home *** CD-ROM | disk | FTP | other *** search
/ Spec Disk 1998 Spring 4.0 / Spec Disk 1998 Spring 4.0.iso / generic / 13411wfc.gen < prev    next >
Text File  |  1998-06-10  |  6KB  |  165 lines

  1.     SECTION 13411
  2.  
  3.     INSTRUMENT CONSOLES
  4. NOTE ** Warminster Fiberglass Co. instrument consoles.
  5. NOTE ** 
  6. NOTE ** This section is based on products manufactured by Warminster Fiberglass Co., which is located at the following address:
  7. NOTE **     P.O. Box 188
  8. NOTE **     Southampton PA  18966-0188
  9. NOTE **     Tel:  (215) 953-1260
  10. NOTE **     Fax:  (215) 357-7893
  11. NOTE ** 
  12. NOTE ** Warminster Fiberglass Co. has manufacturing facilities in Southampton PA and in Jacksonville TX, and manufactures a wide line of fiberglass reinforced polyester resin products for the water and waste treatment industry, including instrument consoles, Palmer-Bowlus flumes, Parshall flumes, slide gates, wash troughs, effluent troughs, finger weirs, weir plates, scum baffles, metering manholes, density current baffles, and odor control systems.
  13. NOTE ** 
  14. NOTE ** Warminster also manufactures fiberglass doors and frames and buildings, shelters, and enclosures for a wide range of uses.
  15. NOTE ** 
  16. NOTE ** SECTION 13411 - INSTRUMENT CONSOLES, Copyright 1997, The Architect's Catalog, Inc.
  17.  
  18.  
  19. PART 1    GENERAL
  20.  
  21. 1.1    SECTION INCLUDES
  22.  
  23.     A.    Instrument consoles.
  24.  
  25. 1.2    RELATED SECTIONS
  26. NOTE ** Delete any sections below not relevant to this project; add others as required.
  27.  
  28.     A.    Section 03300 - Cast-In-Place Concrete.
  29.  
  30.     B.    Section 08342 - Fiberglass Doors and Frames.
  31.  
  32.     C.    Section 11201 - Wash Troughs.
  33.  
  34.     D.    Section 11202 - Effluent (Collection) Troughs (Launders).
  35.  
  36.     E.    Section 11203 - Finger Weir Pans.
  37.  
  38.     F.    Section 11204 - Weir Plates, Scum Baffles, and Brackets.
  39.  
  40.     G.    Section 11205 - Density Current Baffle System.
  41.  
  42.     H.    Section 11206 - Palmer-Bowlus Flumes.
  43.  
  44.     I.    Section 11207 - Parshall Flumes.
  45.  
  46.     J.    Section 11208 - Metering Manholes.
  47.  
  48.     K.    Section 11286 - Slide Gates and Guides.
  49.  
  50.     L.    Section 11305 - Odor Control System.
  51.  
  52.     M.    Section 13122 - Pre-Engineered Fiberglass Buildings.
  53.  
  54. 1.3    REFERENCES
  55. NOTE ** Delete references from the list below that are not actually required by the text of the edited section.
  56.  
  57.     A.    ASTM D 638 - Standard Test Method for Tensile Properties of Plastics.
  58.  
  59.     B.    ASTM D 790 - Standard Test Methods for Flexural Properties of Unreinforced and Reinforced Plastics and Electrical Insulating Materials.
  60.  
  61. 1.4    SUBMITTALS
  62.  
  63.     A.    Submit under provisions of Section 01300.
  64.  
  65.     B.    Product Data:  Test results of fiberglass reinforced plastic laminate.
  66.  
  67.     C.    Shop Drawings:  Show:
  68.         1.    Critical dimensions, jointing and connections, fasteners and anchors.
  69.         2.    Materials of construction.
  70.         3.    Sizes, spacing, and locations of structural members, connections, attachments, openings, fasteners, and loads.
  71.  
  72.     D.    Samples:  8-inch square sample of fiberglass reinforced plastic laminate.
  73.  
  74.     E.    Manufacturer's installation instructions.
  75.  
  76. 1.5    DELIVERY, STORAGE, AND HANDLING
  77.  
  78.     A.    Store products indoors and protect from construction traffic and damage.
  79.  
  80. PART 2    PRODUCTS
  81.  
  82. 2.1    MANUFACTURER
  83.  
  84.     A.    Provide products manufactured by Warminster Fiberglass Company; P.O Box 188, Southampton PA 18966-0188; ASD.  Tel. (215) 953-1260, Fax. (215) 357-7893.
  85. NOTE ** Delete one of the two following paragraphs; coordinate with Division 1 requirements.
  86.  
  87.     B.    Requests for substitution will be considered in accordance with provisions of Section 01600.
  88.  
  89.     C.    Substitutions:  Not permitted.
  90.  
  91. 2.2    INSTRUMENT CONSOLES
  92.  
  93.     A.    Fiberglass Material:
  94.         1.    Tensile strength (ASTM D 638):  9,000 psi.
  95.         2.    Flexural strength (ASTM D 790):  15,000 psi.
  96.         3.    Flexural modulus (ASTM D 790):  900,000 psi.
  97.  
  98.     B.    Construction:  Totally enclosed molded fiberglass reinforced plastic instrument panels.
  99.         1.    One-piece molded construction.  No metal strips required to form mechanical joints.
  100.         2.    Smooth gloss, gel-coated outside surfaces; no exposed glass fibers.
  101.         3.    1/2 inch radius rounded corners; cutout edges sanded and smooth.
  102.         4.    Recessed, lift-off access doors with Southco Type 44 latches.
  103.         5.    Nominal wall thickness, instrument mounting surface:  1/4 inch.
  104.         6.    Nominal wall thickness, elsewhere:  1/8 inch.
  105.         7.    Access doors:  Front and rear.
  106.         8.    Open bottom construction; 2-1/2 inch mounting flange and factory drilled anchor holes.
  107. NOTE ** Delete one of the following two paragraphs.  Beige is the standard color.  Enter other color in the blank.
  108.         9.    Color:  Beige.
  109.         10.    Color:  _______________.
  110. NOTE ** Delete models, below, that are not required.
  111.         11.    Table-top type, 36 inches wide:  Model WFC1010BB.
  112.         12.    Table-top type, 48 inches wide:  Model WFC1015BB.
  113.         13.    Table-top type, 66 inches wide:  Model WFC1020BB.
  114.         14.    Low breakfront type, 36 inches wide:  Model WFC1010CB.
  115.         15.    Low breakfront type, 48 inches wide:  Model WFC1015CB.
  116.         16.    Low breakfront type, 66 inches wide:  Model WFC1020CB.
  117.         17.    High breakfront type, 36 inches wide:  Model WFC1010DB.
  118.         18.    High breakfront type, 48 inches wide:  Model WFC1015DB.
  119.         19.    High breakfront type, 66 inches wide:  WFC1020DB.
  120. NOTE ** The following paragraphs are optional.
  121.         20.    Surface finish:  Matte.
  122.         21.    Surface finish:  Satin.
  123.         22.    Gasket on door.
  124.         23.    Galvanized power struts.
  125.         24.    Fiberglass power struts.
  126.         25.    Instrument cut-outs.
  127.         26.    1/4 inch thick fiberglass sub-panel, mounted on power struts.
  128.         27.    1/8 inch thick steel sub-panel, mounted on power struts.
  129.  
  130. PART 3    EXECUTION
  131.  
  132. 3.1    EXAMINATION
  133.  
  134.     A.    Verify that dimensions are correct and project conditions are suitable for installation.  Do not proceed with installation until unsatisfactory conditions have been corrected.
  135.  
  136. 3.2    INSTALLATION
  137.  
  138.     A.    Install products in accordance with manufacturer's instructions.
  139.  
  140.     B.    Ensure that products are installed plumb and true, free of warp or twist, within tolerances specified by the manufacturer and as indicated in the contract documents.
  141. NOTE ** A 2 inch raised concrete pad is recommended for housekeeping, and will bring front edge of consoles to a 36 inch height above finished floor.
  142.  
  143.     C.    Anchor consoles to floor with expansion anchors.
  144.  
  145. 3.3    ADJUST AND CLEAN
  146.  
  147.     A.    Clean surfaces in accordance with manufacturer's instructions.
  148.  
  149.     B.    Remove trash and debris, and leave the site in a clean condition.
  150.  
  151.     END OF SECTION
  152. ??
  153.  
  154.  
  155.  
  156.  
  157.  
  158.  
  159.  
  160.  
  161.  
  162.     13411-1